American Wire Guage Table and AWG Electrical Current Load Limits
From somewhere on CSGNetwork.com
AWG Wire Sizes (see table below)![]()
![]()
AWG: In the American Wire Gauge (AWG), diameters can be calculated by applying the formula D(AWG)=.005·92((36-AWG)/39)
inch. For the 00, 000, 0000 etc. gauges you use -1, -2, -3, which makes
more sense mathematically than "double nought." This means that in
American wire gage every 6 gauge decrease gives a doubling of the wire
diameter, and every 3 gauge decrease doubles the wire cross sectional
area. Just like dB in signal levels.
| AWG gauge | Diameter Inches | Diameter mm | Ohms per 1000 ft | Ohms per km | Maximum amps for chassis wiring | Maximum amps for power transmission |
| OOOO | 0.46 | 11.684 | 0.049 | 0.16072 | 380 | 302 |
| OOO | 0.4096 | 10.40384 | 0.0618 | 0.202704 | 328 | 239 |
| OO | 0.3648 | 9.26592 | 0.0779 | 0.255512 | 283 | 190 |
| 0 | 0.3249 | 8.25246 | 0.0983 | 0.322424 | 245 | 150 |
| 1 | 0.2893 | 7.34822 | 0.1239 | 0.406392 | 211 | 119 |
| 2 | 0.2576 | 6.54304 | 0.1563 | 0.512664 | 181 | 94 |
| 3 | 0.2294 | 5.82676 | 0.197 | 0.64616 | 158 | 75 |
| 4 | 0.2043 | 5.18922 | 0.2485 | 0.81508 | 135 | 60 |
| 5 | 0.1819 | 4.62026 | 0.3133 | 1.027624 | 118 | 47 |
| 6 | 0.162 | 4.1148 | 0.3951 | 1.295928 | 101 | 37 |
| 7 | 0.1443 | 3.66522 | 0.4982 | 1.634096 | 89 | 30 |
| 8 | 0.1285 | 3.2639 | 0.6282 | 2.060496 | 73 | 24 |
| 9 | 0.1144 | 2.90576 | 0.7921 | 2.598088 | 64 | 19 |
| 10 | 0.1019 | 2.58826 | 0.9989 | 3.276392 | 55 | 15 |
| 11 | 0.0907 | 2.30378 | 1.26 | 4.1328 | 47 | 12 |
| 12 | 0.0808 | 2.05232 | 1.588 | 5.20864 | 41 | 9.3 |
| 13 | 0.072 | 1.8288 | 2.003 | 6.56984 | 35 | 7.4 |
| 14 | 0.0641 | 1.62814 | 2.525 | 8.282 | 32 | 5.9 |
| 15 | 0.0571 | 1.45034 | 3.184 | 10.44352 | 28 | 4.7 |
| 16 | 0.0508 | 1.29032 | 4.016 | 13.17248 | 22 | 3.7 |
| 17 | 0.0453 | 1.15062 | 5.064 | 16.60992 | 19 | 2.9 |
| 18 | 0.0403 | 1.02362 | 6.385 | 20.9428 | 16 | 2.3 |
| 19 | 0.0359 | 0.91186 | 8.051 | 26.40728 | 14 | 1.8 |
| 20 | 0.032 | 0.8128 | 10.15 | 33.292 | 11 | 1.5 |
| 21 | 0.0285 | 0.7239 | 12.8 | 41.984 | 9 | 1.2 |
| 22 | 0.0254 | 0.64516 | 16.14 | 52.9392 | 7 | 0.92 |
| 23 | 0.0226 | 0.57404 | 20.36 | 66.7808 | 4.7 | 0.729 |
| 24 | 0.0201 | 0.51054 | 25.67 | 84.1976 | 3.5 | 0.577 |
| 25 | 0.0179 | 0.45466 | 32.37 | 106.1736 | 2.7 | 0.457 |
| 26 | 0.0159 | 0.40386 | 40.81 | 133.8568 | 2.2 | 0.361 |
| 27 | 0.0142 | 0.36068 | 51.47 | 168.8216 | 1.7 | 0.288 |
| 28 | 0.0126 | 0.32004 | 64.9 | 212.872 | 1.4 | 0.226 |
| 29 | 0.0113 | 0.28702 | 81.83 | 268.4024 | 1.2 | 0.182 |
| 30 | 0.01 | 0.254 | 103.2 | 338.496 | 0.86 | 0.142 |
| 31 | 0.0089 | 0.22606 | 130.1 | 426.728 | 0.7 | 0.113 |
| 32 | 0.008 | 0.2032 | 164.1 | 538.248 | 0.53 | 0.091 |
| Metric 2.0 | 0.00787 | 0.200 | 169.39 | 555.61 | 0.51 | 0.088 |
| 33 | 0.0071 | 0.18034 | 206.9 | 678.632 | 0.43 | 0.072 |
| Metric 1.8 | 0.00709 | 0.180 | 207.5 | 680.55 | 0.43 | 0.072 |
| 34 | 0.0063 | 0.16002 | 260.9 | 855.752 | 0.33 | 0.056 |
| Metric 1.6 | 0.0063 | 0.16002 | 260.9 | 855.752 | 0.33 | 0.056 |
| 35 | 0.0056 | 0.14224 | 329 | 1079.12 | 0.27 | 0.044 |
| Metric 1.4 | .00551 | .140 | 339 | 1114 | 0.26 | 0.043 |
| 36 | 0.005 | 0.127 | 414.8 | 1360 | 0.21 | 0.035 |
| Metric 1.25 | .00492 | 0.125 | 428.2 | 1404 | 0.20 | 0.034 |
| 37 | 0.0045 | 0.1143 | 523.1 | 1715 | 0.17 | 0.0289 |
| Metric 1.12 | .00441 | 0.112 | 533.8 | 1750 | 0.163 | 0.0277 |
| 38 | 0.004 | 0.1016 | 659.6 | 2163 | 0.13 | 0.0228 |
| Metric 1 | .00394 | 0.1000 | 670.2 | 2198 | 0.126 | 0.0225 |
| 39 | 0.0035 | 0.0889 | 831.8 | 2728 | 0.11 | 0.0175 |
| 40 | 0.0031 | 0.07874 | 1049 | 3440 | 0.09 | 0.0137 |
![]()
![]()
![]()
|
The following calculator calculates the voltage drop, and voltage at the end of the wire for American Wire Gauge from 4/0 AWG to 30 AWG, aluminum or copper wire. (Note: It just calculates the voltage drop, consult the above table for rules-of-thumb, or your local or national electrical code or your electrician to decide what is legal!)
|
||||
This chart of American Wire Gauge (AWG) wire sizes and rated ampacities is data intended for the pleasure of our readers only. Typographical errors, etc. are probable, since the typist is not a professional (our CEO). Please point out errors. The data listed are incomplete and should be used as a guideline only. Please contact manufacturers for the latest data.
We hope that this information is helpful. Now go out and design something that needs a charger, power supply, or battery pack!
NOTE: All of this came from:
|